Скачать книгу

conditions) with wind‐based DERs [27]. Power systems are traditionally designed for unidirectional power flow. However, with the growing installations of DERs, power can flow potentially in a bidirectional manner.

      Wind typically blows during nighttime, as in Ontario, Canada. In feeders where wind farms are connected, reverse power flow usually occurs during night since loads are much lower during nighttime as compared to daytime. Such reverse flow of power causes voltages to rise in the feeder that may exceed acceptable limits during the prevalent light‐loading conditions.

Schematic illustration of a realistic distribution feeder in Ontario. Schematic illustration of PCC bus voltages for various solar farm output cases with increasing wind farm output.

      Protection and relaying systems, voltage regulators, LTCs with line drop compensation, are typically designed for one way flow of power. Reverse power flow, therefore, adversely impacts the operation of such systems. High amount of reverse power flows may cause interruption rating of the circuit protection systems to be exceeded as well as cause sympathetic tripping of adjacent circuits.

      Sectionalizers and fault indicators that are commonly used in distribution systems are based on radial flow of power. They can misoperate in scenarios where power flow can change direction. These radial devices need to be replaced or reconfigured, else they may provide erroneous information about fault locations making system restoration difficult [26].

      Voltage regulators, even if they are reconfigured for bidirectional power flow, can only control the voltage in close vicinity. They are unable to regulate the voltage between the regulator and the DER when voltage increases occur due to reverse power flow [26]. The customers near the DER may still experience high voltages in cases of large reverse flow due to high penetration of DERs.

      To circumvent these issues due to reverse power flow, the protection system settings, voltage regulators, and tap changer operations must be reconfigured to respond correctly during bidirectional power flows. In case of reverse power flow in single‐phase systems, phase balancing must be pursued as a mitigation measure [24].

      However, there are many distribution systems having large PV plants where reverse power flow routinely occurs and the protection systems are well‐designed to handle such normal operations.

      1.2.4 Transient Overvoltage

      Unsymmetrical faults, such as single‐line‐to‐ground faults, on DER connected distribution lines, can cause Transient Overvoltages (TOVs) [27]. TOVs may also be caused by sudden connection or tripping of DERs, tripping of downstream feeders or loads, large and sudden fluctuations of DER power output due to cloud passage/wind flow changes [27]. The magnitude of TOV is, of course, dependent upon the connection scheme of the coupling transformers (start‐star, star‐delta, etc.) [42]. These TOVs can potentially have a damaging impact on other equipment connected to the distribution line.

      The magnitude of TOV is seen to increase with the number of DER connections or increasing power output from the DERs. For this reason, utilities often impose a restriction on the number of DERs to be connected to their distribution feeders based on this criterion.

      Transient overvoltages are evaluated for nighttime and three solar farm output cases (0, 50, and 98% solar farm output) during daytime. The maximum wind power that can be integrated into the grid without violating TOV limit of 1.3 pu in the grid is 11.1 MW for Case 1, 5.4 MW for Case 2, and 2.1 MW for Case 3. During nighttime, when the load is lowest, the maximum wind power output permissible is only 3.96 MW. It is noted that the TOV criterion restricts the DER connectivity even more than the steady‐state voltage criterion.

Schematic illustration of TOV in PCC phase voltages for fault at load end.

      The above TOV situation can be avoided by using transformers of different configurations which provide an effective grounding on the feeder side. One of the mechanisms of limiting TOVs is the use of grounding transformers or a fast ground overvoltage protection strategy [21] to prevent supply of power to the loads on an ungrounded system after a fault or unplanned switching event. Recently, SVCs have been employed to mitigate TOVs in wind farms [45].

      1.2.5

Скачать книгу