Скачать книгу

burn hazardous wastes as supplemental fuel under 40 CFR 266 (U.S. EPA 2020i). This program under RCRA is delegated for management by the states. For hazardous waste incinerators, initial trial burns of hazardous pollutants are used to set operating criteria for the facilities. In many permits, the CEM system is tied into the operating system, where feed is cut off if CO or THC levels exceed the established trigger levels, or if the O2 concentration decreases below the established limits. This is done, in part, to address the public's concern regarding emissions from such facilities.

      BIF continuous emission monitoring requirements are found for CO in 40 CFR 266 §266.104(b)(2) and hydrocarbons (HC) in [§266.104(c)((3)]. In the BIF rules, performance specification for CO analyzers are given in Part 266 Appendix IX §2.1 and for hydrocarbon analyzers in §2.2. The performance specifications for CO are similar to those given in 40 CFR 60 Appendix B Performance Specification 4a. A relative accuracy test is not required for Part 266 hydrocarbon analyzers.

      Quality assurance requirements for Part 266 CO and HC monitoring systems are found in Appendix IX of Part 266, where daily calibration checks, daily system audits, quarterly calibration error (linearity) tests, and an annual performance specification tests are required. Conducting an annual performance specification test for the CO monitoring system implies that a seven‐day calibration drift test, in addition to a response time test and a RATA, would be required, in contrast to Part 60 Appendix F where only an annual RATA is required (U.S. EPA 2020e).

      Monitoring requirements have also been promulgated for hazardous waste combustors under the MACT standards of 50 CFR 63 Subpart EEE. Section 63.1209(a) (ii) requires that either a CO or hydrocarbon analyzer be installed, along with an oxygen monitor, to report emissions corrected to 7% O2. Cement kilns burning hazardous waste are also required to install a continuous opacity monitoring system (COMS).

       Sewage Sludge Incineration (40 CFR 503)

      EPA regulations concerning sludge management programs are found under Title 40 Subchapter O – Sewage Sludge and Part 501: State Sludge Management Program Regulations. Regulatory authority is given under the Clean Water Act, which requires that states must develop sludge management programs. Part 501 specifies the requirements that a State program must meet for it to be approved by EPA. Sewage sludge can be disposed of in a solid waste landfill, applied to the land, or incinerated. For landfill or land applications, limits for metal concentrations, loading levels, and pathogen density are specified.

      New sewage sludge incinerators are also regulated under New Source Performance Standard Subpart O if the incinerator was constructed after 11 June 1973. The regulation requires the installation of an oxygen analyzer only. Here, the instrument specifications require a ±5% relative accuracy as certified by the manufacturer and a calibration every 24 hours according to manufacturer procedures. No reference is made to the Part 60 Appendix B or Appendix F CEM requirements, which are more complete.

      State Programs and Federal Programs Administered by the States

      State environmental control agencies are tasked with federal requirements to meet ambient air standards for SO2, NOx, ozone, and particulate matter as PM2.5. The states receive federal funding for this purpose and institute programs to monitor ambient air concentrations of these ambient pollutants. Ambient air monitoring shelters housing analyzers that use many of the same analytical techniques as CEM systems are located across the country, providing a continuous assessment of ambient air quality.

      By applying established regulatory procedures, CEM systems can also be required to be installed on other source categories or used directly for compliance. The development of such regulations typically proceeds through public hearings, combined with many approval processes. Under these procedures, it can often take several years before a regulation is issued.

       State Implementation Plan Requirements (40 CFR 5l)

      Each state is required by the U.S. Clean Air Act to have a State Implementation Plan, or SIP, that will lead to the improvement and maintenance of the air quality such that all areas of the state will meet national ambient air quality standards. Federal requirements for SIPs are given in 40 CFR 51 – Requirements for Preparation, Adoption, and Submittal of Implementation Plans and 40 CFR 52 – Approval and Promulgation of Implementation Plans (U.S. EPA 2020b).

Federal Programs Delegated to States
SIP Rulemaking Permit Programs NSPS Delegation SIP Rulemaking Compliance Assurance Monitoring Waste Incineration Trading Programs Discretionary

Скачать книгу